M22 is the size almost nobody designs in and a great many people end up buying. It sits between two first-choice sizes, M20 and M25, and it exists because metric thread standards offer a second series of intermediate diameters for exactly this purpose. On paper that makes it optional. On a real panel it is often the only thread that fits, because the hole was already there and the cable was 14 mm.
This page covers what M22 will and will not do: the five dimensions behind the number, why it is the smallest thread that reaches a 14 mm sheath, where it is interchangeable with M25 and PG16 and where it is not, and why the same nominal size has a different hole in brass than in nylon. For the size either side see the M20 size guide and the M25 size guide.
An M22 gland is an M22 x 1.5 metric thread with a 10 to 14 mm cable range, a mounting hole of 22 to 22.2 mm, 8 mm of thread length and a 24 mm spanner. It seals on a face washer under the locknut and grips the sheath with a compressed insert under the dome nut, like every other straight gland in the range.
The number that matters most is not 22. It is the 10 to 14 mm band, because that is what the fitting does and what nothing else in the small sizes can do at this hole diameter.
Metric threads are published in a first series and a second series. The first series carries the sizes you would choose on a clean sheet: M20, M25, M32, M40, M50, M63. The second series fills the gaps at roughly three to four millimetre intervals, and M22 is one of those fillers, along with M24, M28, M30, M33, M37, M42 and M48.
That history explains the practical situation. You meet M22 in three ways: an existing 22 mm hole you are not going to ream, a drawing inherited from a supplier who works in the second series, or a cable of 13 to 14 mm where M20 is too small. In all three the size is a constraint to be accommodated, and the question is which other sizes can share that constraint, not whether M22 is theoretically preferable.
| Dimension | M22 value | What it decides |
|---|---|---|
| Thread | M22 x 1.5 | The pitch is part of the specification; a locknut or adapter must match it |
| Cable range | 10 to 14 mm | Sheath outside diameter, measured, not the sum of core diameters |
| Thread outside diameter | 22 mm | Drives the hole |
| Mounting hole | 22 to 22.2 mm | Thread diameter plus 0.2 mm, as across the metal range |
| Thread length GL | 8 mm | Must exceed panel plus washer plus locknut plus any earth tag |
| Bonding length | 23 mm | How much sheath ends up inside the body |
| Spanner size | 24 mm | The same wrench as M24 and M25 |
Four threads in this catalogue cover the 10 to 14 mm cable band, so the cable does not choose between them. The hole does. And the hole is where two of them stop being interchangeable without any visible sign on the drawing.
| Size | Thread O.D. | Mounting hole | Cable range | Shares a 22 mm hole? |
|---|---|---|---|---|
| M22 | 22 mm | 22 to 22.2 mm | 10 to 14 mm | Yes, this is its own hole |
| PG16 | 22.5 mm | 22.5 to 22.7 mm | 10 to 14 mm | No: 0.5 mm too large |
| M24 | 24 mm | 24 to 24.2 mm | 10 to 14 mm | No |
| M25 | 25 mm | 25 to 25.2 mm | 10 to 14 mm | No |
PG16 is the dangerous one, because it is the closest neighbour and covers exactly the same cable. Its thread is half a millimetre larger. A hole drilled at 22.5 mm will not seal an M22 gland, because the face washer cannot bridge the gap and simply extrudes outwards under compression. A hole at 22 mm will not accept PG16 at all. Two fittings that look like a straight swap on a cable list are a 0.5 mm decision on the panel, and no amount of tightening fixes the wrong side of it.
The useful comparison is not thread diameter but what the thread length buys. M22 carries M20’s 8 mm of thread and M25’s 10 to 14 mm cable range in the same fitting.
| M20 | M22 | M25 | |
|---|---|---|---|
| Cable range | 6 to 12 mm | 10 to 14 mm | 10 to 14 mm |
| Thread length GL | 8 mm | 8 mm | 9 mm |
| Bonding length | 22 mm | 23 mm | 25 mm |
| Spanner | 22 mm | 24 mm | 24 / 27 mm |
| Mounting hole | 20 to 20.2 mm | 22 to 22.2 mm | 25 to 25.2 mm |
That combination is M22’s only genuine engineering advantage. Where the panel is thin enough that M25’s 9 mm of thread is marginal, and the cable is 13 or 14 mm, M22 keeps the thread length of the smaller size and still grips the cable. It is a narrow case, but it is the one where M22 is the correct answer rather than the inherited one.
M20 stops at 12 mm on this range, and that is the single most common reason a project moves to M22. A 14 mm sheath is 2 mm outside what M20 can seal, and forcing it produces the failure that looks like a gland fault and is really a sizing fault: the insert cannot compress, the dome nut bottoms out on the body, and the cable slides rather than being gripped.
Moving up from M20 to M22 rather than to M25 keeps the hole at 22 mm instead of 25 mm, which matters on a gland plate that is already drilled, on a terminal box with limited face area, and wherever entry spacing between adjacent glands is tight. The 3 mm saved per entry is the difference between fitting a row and not fitting it.

Eight millimetres of GL is not much. Panel thickness plus flat washer plus locknut plus any earth tag has to come in under it, and at M22 that budget is spent quickly on a stiffened enclosure wall. Check the parts rather than assuming a standard stack: the gland that engages two turns will hold, and will not seal.
There is a practical workaround worth knowing. Where the wall is too thin to give the gland a proper bearing face, the failure is usually the panel deflecting rather than the thread being short, and a machined backing pad solves both at once. Where the wall is genuinely thick, the answer is a longer-thread variant of the same thread rather than a larger size, because the cable range does not need to change.
M22 in nickel-plated brass is drilled at 22 to 22.2 mm. M22 in moulded polyamide is drilled at 22.2 to 22.5 mm. The cable range is identical at 10 to 14 mm and the thread is the same nominal 22 x 1.5, so the two look like a material substitution on a bill of materials. They are not a hole substitution.
A hole at 22.0 mm will not take the nylon body at all. A hole at 22.5 mm will take the nylon body and will not seal the brass one. Metal bodies are machined and hold a tighter tolerance; moulded bodies need more clearance for draft and shrinkage, and that difference is designed in rather than a defect. If a material change is still possible late in a project, the hole should be drilled to the tighter of the two and opened later if the nylon part is chosen, never the other way round.

M22, M24 and M25 all take a 24 mm spanner across the body. For a panel builder that is a genuine simplification: one wrench covers three thread sizes and the entire 10 to 14 mm cable band, so a kit does not have to carry a separate tool for each entry size.
It also creates a maintenance risk. Because the same wrench fits all three, an installer who finds a loose gland cannot tell from the tool which thread they are tightening, and over-tightening a nylon M22 to the feel of a brass M25 is easy. Check the fitting rather than the wrench, and where the body is plastic, stop at the point the insert grips rather than at the point the nut stops moving.
| Field | What to state | Why it matters |
|---|---|---|
| Thread | M22 x 1.5, not “M22” | The pitch decides whether existing locknuts and adapters fit |
| Cable range | The measured sheath diameter | 10 to 14 mm is a band; a cable at either end behaves differently |
| Material and grade | Nickel-plated brass, 304 or 316L, or polyamide | Sets the hole tolerance as well as the corrosion answer |
| Hole | 22 to 22.2 mm metal, 22.2 to 22.5 mm nylon | The two are not interchangeable in the panel |
| Thread length | GL 8 mm, or the panel stack it must clear | The shortest budget in this size band |
| Sealing | IP rating and the wet condition | IP68 alone does not define a depth or a duration |
| Accessories | Locknut, washer and earth tag as separate lines | They consume the same 8 mm of thread |
M22 appears across the metal ranges and the moulded ranges rather than on a single product page. The brass sizes are listed in the standard metric brass series, the stainless equivalents in the stainless steel range, and the moulded versions in the nylon cable gland range. Where an entry has to turn a corner rather than run straight, the same thread is available as a 90 degree elbow gland. For every size in one place, use the cable gland thread size chart.
10 to 14 mm sheath outside diameter. Measure the finished cable across the sheath rather than adding conductor diameters together, and keep a millimetre clear of either end of the band.
22 to 22.2 mm in metal. The moulded nylon version needs 22.2 to 22.5 mm, so a hole drilled for brass may be too tight for nylon.
No. Both cover 10 to 14 mm cable, but M22 has a 22 mm thread and PG16 has 22.5 mm, so they need different holes and cannot be substituted once the panel is drilled.
Often yes, since both cover 10 to 14 mm, provided the hole is 22 mm rather than 25 mm. M22 also has 1 mm less thread length, which matters on a thick or stiffened panel.
Because the face washer cannot bridge the extra clearance. It extrudes outwards instead of compressing against the panel, so tightening makes the leak worse. The fix is a stepped washer or a welded pad, not more torque.