A high temperature cable gland is rarely sold as a temperature problem. It is sold as a stainless steel gland, and the temperature figure follows it in the catalogue. That figure is usually the limit of one component inside the assembly, and it is almost never the metal.
The practical consequence is that two suppliers can quote very different numbers for what looks like the same part, and both can be telling the truth — one is quoting the housing, the other the seal. This article is about working out which number applies to your installation, where the heat actually arrives, and what to write on the order so the answer does not change between the sample and the shipment.
A gland in hot service is a chain of four materials, and the installation is only as good as the coolest link. Housing, sealing insert, face washer and cable sheath all see roughly the same heat, and the one with the lowest practical limit defines the assembly.
| Composant | Typical material | What sets the limit |
|---|---|---|
| Housing and thread | Nickel-plated brass, 304 or 316L stainless | Oxidation and strength loss at high temperature; plating integrity |
| Sealing insert | EPDM, NBR, silicone | Compression set and hardening; this is normally the binding constraint |
| Face washer | Same elastomer family as the insert | Same mechanism, but it is compressed against a hot metal face |
| Cable sheath | PVC, PE, XLPE, PUR, silicone | Softening, then embrittlement — and it is the part you cannot replace |
Note the last row. The cable is usually the real limit, and it is the one component the gland supplier does not control. A stainless gland with a silicone insert rated for hot service, gripping a PVC cable rated for a fraction of that, is a hot-service entry on paper only.
Three heat paths reach a gland, and each needs a different answer. Treating them as one number is why hot-service entries fail in furnaces and succeed in ovens with the same reading on the thermometer.
| Path | What it looks like on site | What actually helps |
|---|---|---|
| Radiant | Line of sight to a hot surface; the gland is hot while the air is cool | A shield or a change of angle, not a better seal |
| Convective | Hot air moving through an enclosure or up a duct | Air movement control, enclosure ventilation, distance |
| Conducted | Heat travelling along the metal wall or the cable itself | Thermal break, longer thread run, cable routing |
Radiant heat is what catches people out. A wall-mounted thermocouple reads the air temperature and reports 60 °C; a gland with a direct view of a heated platen six hundred millimetres away can be at twice that. The same asymmetry explains why a gland facing the heat source fails while an identical one on the opposite side of the box gives years of service.

The housing choice is easier than the seal choice, because the two metals behave predictably and the elastomers do not.
Laiton nickelé is the default industrial choice and holds up well in most hot, dry indoor service. Above the range where standard inserts survive, brass becomes the weaker element — not because the metal melts, but because the plating degrades and the assembled rating is set by parts that cannot follow. Stainless steel, 304 or 316L, is the answer when temperature arrives together with corrosion, and it removes the plating question entirely.
Seal selection is where the temperature job is actually decided. Standard nitrile inserts are the usual limiting component. EPDM buys a modest increase and better weathering. Silicone is the material that makes a stainless gland into a high-temperature gland, and it is also the one to specify by name rather than by assumption, because “high temperature version” means different compounds to different factories.
Also check what happens to the seal against the cable, not just against the housing. A silicone insert gripping a PVC sheath at a temperature the silicone tolerates will still leave a softened sheath that has crept out of the seal. The seal materials guide covers compound behaviour in more detail.
An elastomer in a gland is held under compression for years. Heat attacks that state in three stages, and all three are invisible from outside.
This is why a failed hot-service gland often looks serviceable when removed. The metal is bright, the thread is clean, the seal is in position — and it no longer seals. Replacing the insert is a valid repair only if the replacement is the same compound; a standard nitrile ring in a high-temperature gland resets the clock to the shortest interval.
A single maximum temperature is the easiest number to quote and the least informative. What actually ages an entry is the number of cycles and the size of the swing, because each cycle strains the seal and the joint differently.
During heating, the brass or stainless housing expands; so does the steel wall it is fitted to, at a different rate. The seal is compressed by the housing and relieved by the cable, and the net effect of a cycle is a small ratcheting change in compression. Over a few hundred cycles the seal has been worked into a shape it will not recover from. Bake ovens, steriliser doors, engine test cells and foundry equipment all produce this pattern, and all of them defeat a gland chosen on peak temperature alone.
The practical countermeasures are unglamorous: keep the entry away from the hottest zone so the swing is smaller, use a seal with better compression-set behaviour, and increase the maintenance frequency rather than the specification. Where a gland is replaced on a fixed interval regardless of appearance, a cyclic application becomes manageable.
Before choosing a part, get a number that means something. Three rules cover most of the confusion.
Where a permanent instrument is not possible, an irreversible temperature label on the gland body for one production cycle gives a defensible peak figure.
Most hot-service gland problems are solved with geometry rather than with a more expensive part. Three moves, in order of cost.
Change the angle so the entry does not face the heat source; radiant intensity falls with the cosine of the angle and a shield becomes unnecessary. Add a stand-off bracket so the gland sits away from the hot wall and its body is cooled by ambient air rather than heated by conduction. Where neither is possible, a metal shield between the source and the entry — with an air gap — performs better than any wrap applied directly to the gland, because contact wrapping conducts heat into the very part it is meant to protect.

Temperature is the specification most easily lost between quotation and shipment, because it lives in a note rather than in a part number. Write it into the order.
That last point is worth pressing on. An IP68 result obtained at room temperature says little about a gland that will sit at the top of its range; the seal that passes cold is stiffer and less compliant when hot.
Four lines cover most hot-service requirements. The point of the table is the middle column: each line is a different reason for heat, not a different temperature.
| Application | Dominant heat path | What to specify |
|---|---|---|
| Oven or furnace wall entry | Conducted through the wall plus radiant from inside | Stainless housing, silicone insert, stand-off, highest sheath rating available |
| Engine, gearbox or exhaust proximity | Radiant, often intermittent | Stainless housing, shield or re-angle, peak logging before selection |
| Steriliser and wash-down door | Cyclic steam and chemistry | Stainless housing, seal matched to both steam and cleaning agents |
| Enclosure in a hot plant room | Convective ambient | Brass or stainless depending on corrosion; standard seal often adequate |
The metal itself tolerates far more than the assembly. The published range for the finished product is set by the sealing insert and the face washer, so the number to use is the one for the complete part, not for the housing.
Yes, if the replacement is the same compound and the housing has not distorted. A standard nitrile ring in a high-temperature gland returns it to the shortest maintenance interval.
It is the usual answer for dry heat. Where oils, fuels or certain solvents are present, another compound may be the better compromise, and the temperature advantage is worth less than chemical compatibility.
Likely compression set that has already happened, exposed by the heat. The seal stopped sealing earlier and the warmer weather finished the job.
Only if it was tested there. Ask for the test temperature alongside the IP result, and treat a room-temperature result as evidence about the cold condition only. The IP rating guide explains what each digit covers.
Send the measured peak temperature, the cable type and the heat path, and we will say which component sets the limit and whether a standard or high-temperature insert is the honest answer. The stainless steel range covers the housing side; the brass vs stainless comparison covers the choice when temperature and corrosion arrive together.