Bulkhead Cable Glands for Enclosure and Deck Penetrations

Bulkhead Cable Glands for Enclosure and Deck Penetrations

A bulkhead penetration looks like an enclosure wall entry that happens to be thicker. It is not. On an enclosure wall the far side is dry, open and reachable, so one seal on the outside face and a locknut inside is a complete answer. On a bulkhead, deck or tank shell the far side can be wet, blind, or at a different electrical potential, and each of those breaks the standard arrangement in a different way.

This guide works through the three things that change: sealing both faces rather than one, reaching a side that has no access, and bonding across a plate that divides two compartments. It also runs the thread length arithmetic for a bulkhead, where the numbers turn out worse than most drawings assume.

Types of Penetration

The word bulkhead covers several geometries that behave differently. Before choosing hardware it is worth deciding which one the drawing actually shows.

PenetrationWhich faces see waterAccessDefault arrangement
Enclosure wallOne face, normally the outsideBoth sidesGland, washer, locknut
Internal bulkhead or deckEither face, often bothFar side may be blindSeal on both faces, or a boss
Tank or shellProduct side, from inside outBoth sides, one is product contactWasher on the product face
Cofferdam or void between platesBoth faces, and the void itselfNeitherContinuous sleeve, two independent seals

Only the first row is what a catalogue gland is designed for. The other three are why bulkhead entries are usually configured rather than bought off a shelf.

Why One Seal Is Not Enough

A standard gland seals to the panel in one place: the washer trapped between the body shoulder and the panel face. The locknut on the far side is a mechanical clamp with no elastomer and no sealing face.

Locknut, sealing washer, dome nut and threaded barrel of a stainless steel bulkhead cable gland laid out in a row
Four parts, one seal. On a bulkhead that single seal has to serve a plate that can be wet on both faces.

On a second bulkhead the far face can be wet from spray, washdown or a flooded void. Water collects between the locknut and the plate and follows the thread into the space behind it. That space is not the dry compartment, so nothing shows inside, and the plate corrodes from a face nobody inspects. The failure is silent until the paint blisters.

A second seal is therefore a requirement, not an upgrade, wherever both faces can get wet. It can be a washer under the locknut, an O-ring in a counterbore, or a bulkhead fitting with a gasket on each face. What it cannot be is a thread alone.

Which Face Carries the Washer

Where both faces are accessible, the seal belongs on the pressure side. The reason is mechanical: pressure acting on the body from the sealed side pushes the shoulder harder onto the washer, so the load tightens the joint. Pressure from the opposite side lifts the body off the panel and unloads the washer, and a compression seal that is unloaded is not a seal.

Pressure sourceWasher faceEffect on the seal
External: rain, spray, sea, washdownOuter facePressure adds to the clamp load
Internal: tank contents, pressurised voidInner facePressure adds to the clamp load
Alternating: bilge, sloshing, tidalBoth facesTwo seals, each loaded in turn
Immersion from outside with a sealed voidOuter facePressure rises with depth, so does the load

The consequence on a tank is awkward. The pressure side is the inside, so the seal belongs on the inside face, the one that is hardest to reach. Where the inside cannot be reached at all, the washer has to be built into the plate instead.

The Unreachable Side

Some bulkheads have no access from one face: a welded tank, a sealed void, a double-bottom space. A locknut needs a spanner on that side, so it cannot be used, and the choices reduce to five.

MethodWhen it worksWhat it costs
Tapped hole in the platePlate thick enough for four or more full threadsNo seal at the thread, needs sealant or an O-ring
Welded threaded bossSteel plate, welding permitted, distortion tolerableAdds a welded interface that must itself be sealed
Gland plate or insert panelLarge plate, multiple entries, serviceable designTwo more sealed joints per plate
Removable access hatchSpace and inspection regime allow itAn extra opening to seal, and a habit of being left off
Sleeve with two outer sealsVoid between plates, no access to the middleLongest option, and the void must drain somewhere

The tapped hole is the option most often chosen and least thought through. It removes the nut, and replaces a clamped joint with a threaded one that has no elastomer anywhere in it.

Thread Length Across a Bulkhead

Thread length is a budget and a bulkhead spends it faster than a wall. On our stainless PG series GL runs from 7 mm at PG7 to 15 mm at PG63, and the PG13.5 gland that suits most instrument cables has 8 mm. Four items consume that budget: the plate, the washer, the locknut, and two threads left proud of the nut.

The table applies the strict rule: a 1.5 mm washer, a 3 mm thin locknut, and two full threads at the 1.41 mm PG pitch. Figures are rounded down.

TamañoLongitud de la rosca GL (mm)Maximum bulkhead with a 3 mm locknut (mm)
PG770
PG980
PG1180
PG13.580
PG1691
PG1991
PG2191
PG25102
PG29113
PG36124
PG42135
PG48146
PG63157

Derived from the published GL figures of the stainless PG series. Each extra washer, or a 6 mm locknut instead of a 3 mm thin one, takes 3 mm off every line; allowing one thread proud adds 1.4 mm.

Stainless steel thread entering a drilled hole in a thick steel plate, showing the wall depth at the hole
What the plate takes first: thickness at the hole is spent before the washer, the nut or the exposed thread get anything.

Read down the third column: a 6 mm deck cannot be crossed by any standard-thread stainless gland below PG48 with a locknut behind it, on one washer. A bulkhead entry is therefore a long thread gland, a boss, or a tapped hole. The long thread article covers what the longer variant returns size by size.

Tapped Holes and Welded Bosses

A tapped hole gives thread engagement equal to the plate thickness, so the number of full threads is the thickness divided by the pitch. A 6 mm plate at 1.41 mm pitch holds four threads, which is mechanically respectable and hydraulically useless: a parallel thread is a leak path, not a seal. Sealing a tapped entry means an O-ring in a counterbore or a thread sealant on the thread, and sealant on a blind bulkhead makes the joint permanent in practice.

A welded boss solves both: full thread depth, a machined face for the washer, and the sealing face lifted clear of the plate so thickness drops out of the budget. What it does not do is reduce the number of seals. The boss-to-plate weld is now a seal in its own right, and the one inspected least, being on the blind side and under paint.

The honest summary is that no arrangement removes a sealed interface on a blind bulkhead. The choice is only about which interface is easier to reach, inspect and redo.

Compartment Bonding

A metal bulkhead separates compartments, and each side may have its own bonding. The gland bonds to the plate it passes through and nothing else, so the entry becomes a bond point between two zones that may not have been meant to connect.

Bulkhead materialBonding path through the entryWhat to add
Steel, common bond on both sidesBody to plate, plate to structureAn earth tag, recorded on the drawing
Steel, isolated compartmentOnly to the near side plateA bonding jumper to the local bar on the far side
GRP or compositeNone, the plate is an insulatorA separate conductor, and the entry declared isolated
Aluminium structure, stainless glandPath exists but as a dissimilar coupleAn isolating washer, or accept the couple and inspect it

Two duties get confused here. Equipment earthing is about fault current and comes from the protective conductor. Compartment bonding keeps two metallic masses at the same potential so no stray current runs through the structure or the screen. The earthing guide separates them, and the point for a bulkhead is that the gland serves one but not both by accident.

Deck Penetrations on Vessels

A penetration through a watertight deck is a subdivision question before it is a gland question. The opening reduces the integrity of an approved boundary, so position, height and protection are set by the vessel’s subdivision and load line requirements and belong on the penetration schedule before anything is drilled. A correct gland does not make an unapproved hole acceptable.

Two details follow. A single cable uses a gland; a bundle uses a transit block, and forcing eight cables through one large gland produces a seal nobody can verify. The entry should also sit inside a coaming or raised trunk where standing water is possible, because a seal sitting in a puddle is doing immersion duty rather than spray duty. Those depth and time figures are in the submersible gland guide.

Where a void sits between two plates, the two seals must be independent. A single sleeve passing through both, sealed only at its ends, turns the void into a chamber that collects condensate and cannot be drained or inspected. Material selection for the salt side is a separate question, covered in the 316 stainless steel article and the marine cable gland guide.

Ordering and Lead Time

Bulkhead assemblies are rarely a catalogue line. What ships is a gland plus a specified washer set, nut and often an earth tag, so the useful document is an envelope drawing showing which part sits on which face. Ask for it before the order.

On the gama de acero inoxidable the minimum is 300 pieces per size, in one material and one passivation throughout, because a plated nut on a stainless body is a galvanic pair in a wet void. Brass and nylon run at 1,000 pieces per size. Longer thread and non-standard washer combinations are configuration work with their own lead time.

PREGUNTAS FRECUENTES

Can a standard gland be used on a bulkhead with a second washer?

Mechanically yes, and it is the cheapest way to get a seal on both faces. The catch is the thread budget in the table above: the second washer takes 1.5 mm off the available thickness, and small sizes have nothing left to give. Check the arithmetic before committing the hole.

What if the inside face cannot be reached at all?

Then the nut has to go, and the choice is a tapped hole, a welded boss, or a gland plate fitted before the space is closed. All three relocate the seal rather than remove it. There is no arrangement where a blind bulkhead entry has fewer than one sealed interface to maintain.

Does a tapped hole seal on its own?

No. A parallel thread is a leak path with mechanical strength. It needs an O-ring in a counterbore or a thread sealant, and sealant on a blind face makes the joint permanent for practical purposes.

Is a bulkhead fitting different from a cable gland?

Usually it is a gland with sealing faces on both ends and no dome nut at one of them, or a double-ended barrel with a gasket at each face. The giveaway is the datasheet: two sealing faces will be listed separately, along with the thickness range each one covers.

How is a composite bulkhead bonded?

It is not, through the entry. A GRP or composite plate provides no conductive path, so the cable’s screen or armour has to be bonded with a separate conductor taken to the local bonding bar, and the entry should be recorded as isolated on the drawing rather than assumed bonded.

Stainless steel cable gland standing on a diamond plate steel deck with its thread and locknut visible
A deck entry is judged on what happens on both faces of the plate, not on how the gland looks from above.

Entradas relacionadas

ATEX vs IECEx Cable Glands: What Is the Difference?

Prensasestopas ATEX vs. IECEx: ¿Cuál es la diferencia?

Tanto ATEX como IECEx se basan en la norma IEC 60079, pero una es una ley obligatoria de la UE y la otra es voluntaria, y sus procesos de evaluación no son equivalentes. Cómo leer el número de certificado antes de realizar un pedido.

Seguir leyendo
Waterproof Cable Gland Installation Precaution

Precaución de instalación del prensaestopas estanco

Los prensaestopas estancos desempeñan un papel vital en las industrias modernas, especialmente en el sector B2B. No sólo garantizan el sellado de las conexiones de los cables, impidiendo la entrada de agua y polvo, sino que también mejoran la seguridad y estabilidad generales de los sistemas eléctricos. ¿Sabía que una instalación incorrecta de los prensaestopas no sólo puede acortar la vida útil de los equipos [...]

Seguir leyendo