PG9 Cable Gland Size Guide: Range, Hole Size and Dimensions

PG9 Cable Gland Size Guide: Range, Hole Size and Dimensions

A PG9 cable gland is what you reach for when the cable is past control-wire size but nowhere near a motor lead: its seal grips anything from 4 mm to 8 mm. That band is also the most crowded one in any catalogue, which is why the size gets ordered wrong. Two metric sizes cover exactly the same 4 mm to 8 mm, and one of them is functionally identical to PG9 apart from a fraction of a millimetre of thread. This guide gives the five numbers that define a PG9 cable gland and explains the two places it fails on site: the mounting hole and the bottom edge of the cable band. Every dimension comes from this range’s published PG series specification.

PG9 cable gland in nickel-plated brass with a black cable fitted, standing upright
A PG9 body with a 4 mm to 8 mm cable fitted. The size is defined by five numbers, and only one of them relates to the cable.

The Five Numbers Behind “PG9”

The 9 in PG9 is a nominal conduit size, not a dimension you can put a caliper on. The thread outside diameter is 15.2 mm, and the hole it needs is 15.2 mm to 15.4 mm: the thread plus the usual clearance. Those two are what most buyers check, and they are only half the specification.

The remaining three decide whether the gland can be installed at all. Cable range fixes what it seals, thread length decides which wall it passes through, spanner size decides whether you can reach it. Read them in that order.

DimensionPG9 valueWhat it constrains
Cable range4 mm to 8 mmWhat the insert can grip and seal; the cable must sit inside it, not on its limit
Thread outside diameter15.2 mmWhich hole the gland physically enters
Mounting hole15.2 mm to 15.4 mmThe hole to drill or punch; wider and the washer cannot bridge the gap
Thread length GL8 mmWall thickness plus washer plus locknut has to fit inside it
Spanner size18 mm across flatsAccess for tightening, and the pitch you can use between adjacent entries
Longitud de enlace20 mmDepth needed inside the enclosure behind the wall

Three Threads Share One Cable Band

The 4 mm to 8 mm band is not unique to PG9. In the same catalogue the M14, PG9 and M16 entries all state 4 mm to 8 mm. Three threads, three holes, one cable band. The cable therefore cannot be what chooses between them, even though it is the only thing most people quote when they raise an enquiry.

SizeCable rangeD.E. de la roscaMounting holeThread length GLSpanner
PG73 mm to 6.3 mm12.5 mm12.5 mm to 12.7 mm7 mm14 mm
M144 mm to 8 mm14 mm14 mm to 14.2 mm7 mm17 mm
PG94 mm to 8 mm15.2 mm15.2 mm to 15.4 mm8 mm18 mm
M164 mm to 8 mm16 mm16 mm to 16.2 mm8 mm18 mm
PG115 mm to 10 mm18.6 mm18.6 mm to 18.8 mm8 mm20/21 mm

M14 is the budget option of the band, with a 7 mm thread and a 17 mm spanner, so it will not clear a thick panel or a tight pitch. PG9 and M16 are separated by 0.8 mm of thread and nothing else worth mentioning. PG11 starts where PG9 ends.

PG9 and M16 Are the Same Gland on a Different Hole

Set the two rows side by side and five columns match: 4 mm to 8 mm cable range, 8 mm thread length, 20 mm bonding length, 18 mm spanner, same body. The only real difference is the thread, 15.2 mm against 16 mm.

That 0.8 mm decides the order. A 16 mm knockout will not seal a PG9: the thread drops through, the washer sits over a gap it cannot bridge, the body hangs off-centre, and the joint weeps on one side — usually on the first wet day rather than at commissioning. In the other direction a 15.2 mm hole will not accept an M16 at all. Cross-reference charts that print “M16 = PG9” describe the cable range, and the statement holds only while nobody looks at the hole.

Three small metal cable glands of increasing size standing above three matching panel holes
M14, PG9 and M16 all take the same 4 mm to 8 mm cable, but each needs its own hole: 14 mm, 15.2 mm and 16 mm. The cable does not choose between them; the panel does.

So a PG9 enquiry that arrives with an existing panel is really a question about the hole. If it is already punched, the thread is fixed and the cable range is whatever that thread takes. If the hole is still on the drawing, PG9 becomes one of three interchangeable ways to seal the same cable, best chosen on thread length and access.

The 4 mm Edge Is Where PG9 Is the Wrong Answer

A 4 mm to 8 mm range does not mean every cable inside it is equally well served. At 4.0 mm or 4.5 mm the insert sits at the bottom of its travel: it touches the jacket but compresses very little, so sealing pressure and retention are weakest exactly where a small cable is most likely to be pulled. A PG7 covering 3 mm to 6.3 mm, or a moulded M12 covering 3 mm to 6.5 mm, puts the same cable near the middle of the band where the insert has room to hold.

The top edge behaves the same way: a cable measuring 8.0 mm to 8.5 mm should move up to PG11 rather than be forced into a PG9 whose insert is already fully compressed. Specify so the measured jacket lands in the middle half of the range, not on either endpoint.

Measure at three points around the circumference rather than trusting the size printed on the drum. A jacket that reads 8.2 mm one way can read 7.7 mm the other, and the gland seals on the smallest figure.

GL 8 Is Shorter Than It Looks

Thread length is the number that ends a project late. GL 8 mm has to cover the panel, the sealing washer and the locknut in that order, and whatever is left is the margin. On a 5 mm plate there is nothing left.

Wall constructionRough stack-upDoes GL 8 mm work?
1.5 mm sheet, washer, locknut1.5 + 1 + 4 = 6.5 mmYes, with about 1.5 mm spare
3 mm plate, washer, locknut3 + 1 + 4 = 8 mmAt the limit; no margin for a paint film or a second washer
5 mm plate, washer, locknut5 + 1 + 4 = 10 mmNo; needs a long-thread variant or a thinner mounting point
6 mm tapped plate, no locknut6 mmYes; the thread is the only thing in the wall
Insulated panel with a linerLiner plus core plus washerDepends on the liner; check it before drilling
Nickel-plated brass cable gland fitted through the wall of a grey electrical enclosure with the cable entering from outside
A short-thread gland on a thin wall leaves visible thread behind the locknut. On a thick plate the same gland runs out of thread before the nut starts.

Tapped holes change the arithmetic, which is why the same gland can be right on one enclosure and wrong on the next. Where the wall itself is threaded, the thread only has to span the wall, and 8 mm is comfortable to about 6 mm of plate. Where it is a plain hole, the locknut takes its 4 mm out of the same 8 mm and usable wall thickness halves. Use the locknut thickness on the datasheet for the part you buy.

Material Changes the Hole, Not the Cable Range

The same nominal size is a different hole depending on body material. The metal PG9 needs 15.2 mm to 15.4 mm. The moulded nylon M16 states 16.2 mm to 16.5 mm, because a moulded thread runs thicker at the root than a cut one, and nylon M12 needs 12.2 mm to 12.5 mm against the metal M12’s 12 mm.

The flexible version adds a third variable without changing the hole. A PG9 flexible body keeps the 15.2 mm thread and the 4 mm to 8 mm range, but the spanner goes from 18 mm to 19 mm because the neck and dome nut are bulkier. The panel drawing does not change; the layout around it does. Stainless keeps the metal dimensions, so a stainless steel PG9 gland drops into the same hole, while the brass M14 y brass M16 each need their own.

The consequence is a sequencing rule: material first, then hole, then drill. Done the other way round, a workshop ends up with a punched 16 mm hole, a delivery of PG9 glands, and a box of penny washers nobody will sign off.

Spanner 18 and the Pitch Between Holes

18 mm across flats is the smallest size in the range that still gives a wrench something to hold. That matters at the layout more than at the gland: two entries need the spanner body plus a swing arc, not the hole plus a millimetre, so two PG9 glands on 20 mm centres cannot both be tightened.

The same wrench behaves differently by material. On metal the hex is deep and the thread limits torque. On a moulded body the hex is shallower and the plastic yields first, so the force that feels normal on brass rounds a nylon hex.

Five Ways a PG9 Order Goes Wrong

Four of the five patterns below are visible before anything ships.

What happens on siteWhat caused itWhat fixes it
The gland drops through the holeA 16 mm hole drilled for an “M16 equivalent”Re-drill to 15.2 mm to 15.4 mm, or switch the order to M16
Water tracks in at the first rainA 4.2 mm cable sitting at the bottom of the bandMove to PG7 at 3 mm to 6.3 mm, or re-specify so the cable sits mid-band
The locknut will not startAn M16 locknut supplied against a PG9 glandMatch the accessory to the 80 degree PG thread, not the metric one
The thread never reaches the nutGL 8 mm against a thick plate plus washer plus locknutLong-thread variant, or a thinner wall at the entry
The nylon hex rounds offMetal-body tightening habit applied to a moulded bodyTighten to the datasheet figure and stop at seal contact

None of these is a manufacturing fault. Each is a decision taken at the drawing or the purchase order, so the fix always costs more than the gland.

What Belongs on the Drawing and the Purchase Order

Two lines on a drawing prevent most of the failures above: the thread callout with its standard, because PG is an 80 degree thread and a metric nut will appear to fit before it strips, and the hole with a tolerance, 15.2 mm to 15.4 mm rather than “about 15”.

  • Thread: PG9, 80 degree form, with the pitch standard named
  • Cable: measured jacket diameter at three points, stated as a range, with sheath material
  • Body and finish: nickel-plated brass, stainless steel or PA66, plus colour where it matters
  • Hole: 15.2 mm to 15.4 mm, with wall thickness and whether it is tapped or plain
  • Accessories: locknut, sealing washer, shroud or earth tag, each listed rather than assumed

For the same eight columns across every thread system, the cable gland thread size chart covers the whole range. The mounting hole chart gives the hole tolerance for each size, and the difference between 80 and 60 degree threads is in PG versus metric cable glands. The next size up is the PG29 size guide.

Preguntas frecuentes

What cable size does a PG9 cable gland take?

4 mm to 8 mm jacket diameter. That is the sheath, not the conductor, and the seal works best when the measured diameter sits mid-band rather than at either end.

What size hole do I need for a PG9 cable gland?

15.2 mm to 15.4 mm. The thread measures 15.2 mm, and the extra 0.2 mm covers thread tolerance and gives the washer a flat surface. A 16 mm hole is too large.

Is PG9 the same as M16?

For the cable, yes: both cover 4 mm to 8 mm and share the same thread length, bonding length and spanner. For the panel, no: PG9 needs 15.2 mm where M16 needs 16 mm to 16.2 mm.

Can I fit a PG9 gland into an M16 hole?

Only with an adapter or a washer wide enough to bridge the 0.8 mm gap, and neither is a good permanent answer. The gland sits off-centre under load and the seal becomes one-sided.

What is the thread diameter of a PG9 cable gland?

15.2 mm outside diameter. The 9 in the name is a nominal conduit size and does not correspond to any dimension you can measure on the gland.

Entradas relacionadas

EMC Cable Glands for VFD Motors

EMC Cable Glands for VFD Motors

A VFD cable gland has to bond the cable screen around the full circumference at both the drive and the motor end. How to size one for drive cable, where the bond path breaks, and what a gland cannot fix.

Seguir leyendo
Cable Glands for Electrical Enclosures

Cable Glands for Electrical Enclosures

The gland is only as good as the hole it sits in. How wall material, thread length, locknuts, knockouts and gland plates decide whether an enclosure stays at its stated IP rating.

Seguir leyendo